Contact

Products

NN-100 / 110

✔ Compact design saves installation space. The depth is as small as 150 mm, and it can be attached to a commercially available control panel.

Features

● Compact design saves installation space. The depth is as small as 150 mm, and it can be attached to a commercially available control panel.
● Adopting a high angle meter, it is possible to read accurately over a wide range despite its compact size.
● By adopting a relay (AC230V 2.5A) with a large contact capacity, it is possible to operate the pump and solenoid valve directly.

specification

Model NN-100 NN-110
control method ON-OFF control
Measurement range 0~14pH ±700mV
Indicator minimum scale 0.2pH 20mV
accuracy ±1% F・S
input Glass electrode Gold or platinum electrode
Input resistance 5×1011Ω that’s all
Compatible temperature compensation electrode Pt100 –
Transmission output Non-insulated DC4-20mA (load resistance 0-500Ω)
Setting method Upper and lower limit electronic volume setting (set value is indicator monitor method)
Repeat time (T・I) –
Proportional band (P・B) –
Output contacts Upper and lower limits 1c each
Output contact capacity AC230V 2.5A(Resistive load)
Ambient temperature 0~50℃
Power supply AC100V ±10% 50/60Hz
power consumption about 5VA
mass about 1.9kg

Head Office

1-12-11 Tagawakita, Yodogawa-ku,Osaka
532-0021

Overseas Business Department

TEL +81-6-6301-6460
FAX +81-6-6308-3022